Thu 20 Oct, 2016 12:47 pm - yes im sure i got on the phone with a technician from the manufacturer and we ran through the steps together and the code that its throwing is 0010HEX which means its still receiving a start signal. (view)
Thu 20 Oct, 2016 12:44 pm - i found the issue it was still giving the vfd the run command when we tried to stop it so its a plc/sequencing issue (view)
Thu 20 Oct, 2016 11:35 am - i have a VFD that will only shut the pump down to 4%(4hz) when controlled from the control room. when i go to the VFD itself and push the stop button it will finish shutting down all the way. what... (view)